Input | |||
Rated voltage | Voltage range | Action Voltage | |
Minimum starting voltage | Maximum starting voltage | ||
DC 5V 12V 24V | DC 3-32V | DC 2.1V | DC 32V |
AC 100V 220V | AC 90-250V | AC 80V | AC 275V |
Load | ||||||||
Project / Specifications | 10A | 25A | 40A | 60A | 80A | 100A | 120A | 150A |
Rated load voltage | AC 110V 220V 380V 415V 440V | |||||||
Load voltage range | 30-240VAC/90-480VAC |
DC/AC | ||||||||||
Output parameter | ||||||||||
Working voltage(47-63HZ) | 30-240VAC/90-480VAC | Vrms | ||||||||
Transient overvoltage | 1200 | Vpk | ||||||||
Maximum leakage current when disconnected | 0.25 | mAms | ||||||||
dv/dt Minimum when disconnected | 500 | Vμ | ||||||||
Maximum load current | 10 | 25 | 40 | 60 | 80 | 100 | 120 | 150 | Arms | |
(50HZ) One cycle surge current | 170 | 250 | 400 | 750 | 1050 | 1200 | 1800 | 2100 | Apk | |
Maximum pressure drop when conducting | 1.3 | Vp | ||||||||
Maximum use of fuse l2 t | 128 | 340 | 880 | 2520 | 5500 | 6270 | 6270 | 12800 | A2s | |
Substrate thermal resistance | 2.2 | 1.7 | 1.7 | 0.25 | 0.155 | 0.155 | 0.15 | 0.15 | ℃W | |
Controls parameter | ||||||||||
Control voltage range | 3-32 | VDC | ||||||||
Minimum off voltage | 1 | VDC | ||||||||
Maximum input current | 22 | mA | ||||||||
Minimum conduction current | 0.5 | mA | ||||||||
Nominal input impedance | Current Regulted | |||||||||
Maximum conduction timne | 8.33 | ms | ||||||||
Maximum break time | 8.33 | ms | ||||||||
Fundamental characteristics | ||||||||||
Work environment | -20 to 80 | ℃ | ||||||||
Storage environment | -40 to 100 | ℃ | ||||||||
Input to output insulation voltage | 4000 | Vrms | ||||||||
Bottom insulation voltage | 2500 | Vrms | ||||||||
Input to output maximum capacitance | 8 | pF | ||||||||
Guide light color | Green | |||||||||
Product weight | 135 | g |
AC/AC | ||||||||||
Product model: ZG3ND series 10-150Arms | ||||||||||
Output parameter | ||||||||||
Working voltage(47-63HZ) | 30-240VAC/90-480VAC | Vrms | ||||||||
Transient overvoltage | 1200 | Vpk | ||||||||
Maximum leakage current when disconnected | 0.25 | mAms | ||||||||
dv/dt Minimum when disconnected | 500 | Vμ | ||||||||
Maximum load current | 10 | 25 | 40 | 60 | 80 | 100 | 120 | 150 | Arms | |
(50HZ) One cycle surge current | 170 | 250 | 400 | 750 | 1050 | 1200 | 1800 | 2100 | Apk | |
Maximum pressure drop when conducting | 1.3 | Vp | ||||||||
Maximum use of fuse l2 t | 128 | 340 | 880 | 2520 | 5500 | 6270 | 6270 | 12800 | A2s | |
Substrate thermal resistance | 2.2 | 1.7 | 1.7 | 0.25 | 0.155 | 0.155 | 0.15 | 0.15 | ℃W | |
Controls parameter | ||||||||||
Control voltage range | 90-280 | VDC | ||||||||
Minimum off voltage | 10 | VDC | ||||||||
Maximum input current | 10 | mA | ||||||||
Minimum conduction current | 5 | mA | ||||||||
Nominal input impedance | Current Regulted | |||||||||
Maximum conduction timne | 20 | ms | ||||||||
Maximum break time | 30 | ms | ||||||||
Fundamental characteristics | ||||||||||
Work environment | -20 to 80 | ℃ | ||||||||
Storage environment | -40 to 100 | ℃ | ||||||||
Input to output insulation voltage | 4000 | Vrms | ||||||||
Bottom insulation voltage | 2500 | Vrms | ||||||||
Input to output maximum capacitance | 8 | pF | ||||||||
Guide light color | Red | |||||||||
Product weight | 135 | g |
Name | Input | Indicator light mode |
Screws | M3.0 mm | M5.0 mm |
Torque | 0.9-1.1 Nm | 1.7-2.3Nm |
ZG3ND series 10-150A | ||
For 10A or more special radiator shall be used | ![]() | |
For 40A, special radiator + cooling fan shall be combined using |
Wiring diagram |
DC-AC |
![]() |
Category | |||||
AC-AC | |||||
Model | Input voltage | Load voltage | Rated load current | Indicator light mode | |
Single-phase panel mounting | ZG3ND-310A | 90-280VAC | 30-240VAC/ 90-480VAC | 10A | Red |
ZG3ND-325A | 25A | ||||
ZG3ND-340A | 40A | ||||
ZG3ND-360A | 60A | ||||
ZG3ND-380A | 80A | ||||
ZG3ND-3100A | 100A | ||||
ZG3ND-3120A | 120A | ||||
ZG3ND-3150A | 150A |
DC-AC | |||||
Model | Input voltage | Load voltage | Rated load current | Indicator light mode | |
Single-phase panel mounting | ZG3ND-310B | 3-32VDC | 30-240VAC/ 90-480VAC | 10A | Green |
ZG3ND-325B | 25A | ||||
ZG3ND-340B | 40A | ||||
ZG3ND-360B | 60A | ||||
ZG3ND-380B | 80A | ||||
ZG3ND-3100B | 100A | ||||
ZG3ND-3120B | 120A | ||||
ZG3ND-3150B | 150A |